三明水泵控制要求:
1. 消防水(shui)(shui)泵(beng)(beng)控制(zhi)柜(ju)應設(she)置在(zai)消防水(shui)(shui)泵(beng)(beng)房或專用消防水(shui)(shui)泵(beng)(beng)控制(zhi)室內(nei),消防水(shui)(shui)泵(beng)(beng)控制(zhi)柜(ju)在(zai)平時應使消防水(shui)(shui)泵(beng)(beng)處于自(zi)動(dong)啟泵(beng)(beng)狀態(tai);當自(zi)動(dong)水(shui)(shui)滅(mie)火系(xi)統為(wei)開(kai)式系(xi)統,且設(she)置自(zi)動(dong)啟動(dong)確(que)有(you)困難時,經論證后消防水(shui)(shui)泵(beng)(beng)可設(she)置在(zai)手動(dong)啟動(dong)狀態(tai),并應確(que)保24h有(you)人(ren)工(gong)值(zhi)班。

2. 消防(fang)水泵不應(ying)設(she)置自動停(ting)泵的控制(zhi)功(gong)能,停(ting)泵應(ying)由具(ju)有管(guan)理權(quan)限的工(gong)作人(ren)員根據火災撲救情況確定。

三明水泵

3. 消防水泵應確保(bao)從接到啟泵信(xin)號(hao)到水泵正(zheng)常運轉(zhuan)的(de)自動(dong)啟動(dong)時間(jian)不應大于2min 。
4. 消(xiao)防(fang)(fang)水(shui)泵(beng)控(kong)(kong)制柜(ju)應(ying)(ying)設置機械應(ying)(ying)急啟泵(beng)功能,并應(ying)(ying)保證(zheng)在控(kong)(kong)制柜(ju)內的控(kong)(kong)制線路(lu)發生(sheng)故障時(shi)由(you)有管理權限(xian)的人員在緊急時(shi)啟動(dong)消(xiao)防(fang)(fang)水(shui)泵(beng)。機械應(ying)(ying)急啟動(dong)時(shi),應(ying)(ying)確保消(xiao)防(fang)(fang)水(shui)泵(beng)在報警后5.0min內正常(chang)工(gong)作。
5. 消(xiao)防水泵的雙路電(dian)(dian)源自動(dong)(dong)切換時間不應大于2s;當一路電(dian)(dian)源與內燃機(ji)動(dong)(dong)力的切換時間不應大于15s。
6. 消防水泵應能手動(dong)(dong)啟停和(he)自(zi)動(dong)(dong)啟動(dong)(dong)。
7. 消(xiao)防(fang)水泵、穩壓泵應設(she)置就地強制啟停泵按鈕(niu),并(bing)應有(you)保(bao)護裝置。
8. 當消(xiao)防(fang)(fang)(fang)給水(shui)(shui)(shui)(shui)分區(qu)供水(shui)(shui)(shui)(shui)采(cai)用(yong)(yong)轉(zhuan)輸(shu)消(xiao)防(fang)(fang)(fang)水(shui)(shui)(shui)(shui)泵(beng)(beng)(beng)時,轉(zhuan)輸(shu)泵(beng)(beng)(beng)宜在(zai)消(xiao)防(fang)(fang)(fang)水(shui)(shui)(shui)(shui)泵(beng)(beng)(beng)啟(qi)(qi)動后(hou)(hou)(hou)再(zai)啟(qi)(qi)動;當消(xiao)防(fang)(fang)(fang)給水(shui)(shui)(shui)(shui)分區(qu)供水(shui)(shui)(shui)(shui)采(cai)用(yong)(yong)串聯(lian)(lian)消(xiao)防(fang)(fang)(fang)水(shui)(shui)(shui)(shui)泵(beng)(beng)(beng)時,上區(qu)消(xiao)防(fang)(fang)(fang)水(shui)(shui)(shui)(shui)泵(beng)(beng)(beng)宜在(zai)下區(qu)消(xiao)防(fang)(fang)(fang)水(shui)(shui)(shui)(shui)泵(beng)(beng)(beng)啟(qi)(qi)動后(hou)(hou)(hou)再(zai)啟(qi)(qi)動。(采(cai)用(yong)(yong)消(xiao)防(fang)(fang)(fang)水(shui)(shui)(shui)(shui)泵(beng)(beng)(beng)、轉(zhuan)輸(shu)水(shui)(shui)(shui)(shui)箱(xiang)串聯(lian)(lian)系(xi)統(tong)時,從轉(zhuan)輸(shu)水(shui)(shui)(shui)(shui)箱(xiang)吸水(shui)(shui)(shui)(shui)的(de)供水(shui)(shui)(shui)(shui)泵(beng)(beng)(beng)先啟(qi)(qi)動,轉(zhuan)輸(shu)泵(beng)(beng)(beng)后(hou)(hou)(hou)啟(qi)(qi)動;采(cai)用(yong)(yong)水(shui)(shui)(shui)(shui)泵(beng)(beng)(beng)直接串聯(lian)(lian)系(xi)統(tong)時,轉(zhuan)輸(shu)泵(beng)(beng)(beng)先啟(qi)(qi)動,供水(shui)(shui)(shui)(shui)泵(beng)(beng)(beng)后(hou)(hou)(hou)啟(qi)(qi)動)
9. 消(xiao)防(fang)(fang)水泵控制柜設置在專用消(xiao)防(fang)(fang)水泵控制室時,其防(fang)(fang)護等級不應(ying)低(di)于(yu)IP30;與(yu)消(xiao)防(fang)(fang)水泵設置在同一空(kong)間時,其防(fang)(fang)護等級不應(ying)低(di)于(yu)IP55。
10. 消(xiao)防(fang)(fang)(fang)(fang)水(shui)泵控(kong)制(zhi)柜應采(cai)取防(fang)(fang)(fang)(fang)止被水(shui)淹沒的措施。在高溫潮濕(shi)環境下,消(xiao)防(fang)(fang)(fang)(fang)水(shui)泵控(kong)制(zhi)柜內應設置自動防(fang)(fang)(fang)(fang)潮除濕(shi)的裝置。
11. 消(xiao)火(huo)栓按(an)鈕不(bu)宜作為直接(jie)啟(qi)動消(xiao)防水泵的開(kai)關,但可(ke)作為發(fa)出(chu)報警信(xin)號的開(kai)關或啟(qi)動干式消(xiao)火(huo)栓系統的快速啟(qi)閉(bi)裝置等。